1. Start the air supply fan.
2. Open all the gas or oil cocks.
3. Start the automatic ignition sequence.
Danger:
If a burner does not light, and the system does not
shut down automatically, then you must close the
main gas cock on gas burner systems. An uncontrolled
flow of gas can cause fires and explosions.
Do not touch the ignition plug or the ignition wire
when the ignition is on. You will get a shock.
4. Make sure that you can see the flame in the burner system.
If the burner system does not light and
the system does not shut down automatically:
then close the main gas or oil cock manually. DO NOT
operate the system. Go to Checklist after Installation on
page 3-8 and verify the steps. After that, repeat the start
procedure.
the system shut downs automatically:
then see the Trouble-shooting Tables in the next chapter.
4-6
START PROCEDURE
Eclipse Vortometric Burner v2.00, Installation Guide 248, 4/10/07